Reports come as 8½ × 11 sheets, by email, or through our online reporting system. Below is a specimen report on our own lab form — five samples from one unit, and the plain-language call the analyst made each time.

Reading the trend

A single sample tells you the condition of the oil today. Five tell you which direction the equipment is heading — and that is what actually prevents a failure.

Follow silicon across this sheet. It sits flat, then jumps at the third sample: dirt is getting past the air intake. Aluminium and iron climb with it, because abrasive dirt attacks liners and pistons. Sodium stays flat, which rules out a coolant leak and leaves dirt as the explanation. The intake is corrected and the oil changed — and by the fifth sample everything is back to baseline. A repair scheduled, rather than a failure survived.

Specimen data throughout — not an actual customer record.

Specimen report sheet

Specimen oil analysis report: five samples from one diesel generator, showing sample identification, oil condition, and twenty metals in parts per million.
Laboratory Lubriport Labs, Inc. logo 1650 AIRLINE DRIVE, KENNER, LA 70062
(504) 464-1734
Specimen oil analysis report No. 1 ship service generator — 6-cylinder diesel · SAE 40 heavy-duty diesel engine oil · 250-hour sampling interval SPECIMEN — DEMONSTRATION DATA ONLY. NOT AN ACTUAL CUSTOMER RECORD.
Analyst's comment SAMPLE 1 Baseline sample. All wear metals and contamination within normal limits for this unit. Oil suitable for continued use. SAMPLE 2 Wear rates steady and consistent with the previous sample. No abnormal contamination. Continue present drain interval. SAMPLE 3 Silicon markedly elevated, with aluminium and iron rising in step — consistent with dirt entering through the air intake. Check intake ducting and filter seals. Suggest oil change and resample at 250 hours. SAMPLE 4 Silicon much reduced following corrective action. Wear metals trending down and additive levels restored by the oil change. Continue monitoring. SAMPLE 5 All values returned to baseline. No unusual wear or contamination found. Oil suitable for further use.
INVOICE NUMBER LL-20418 LL-20655 LL-20891 LL-21134 LL-21362
REPORT DATE 3/10/2025 5/12/2025 7/14/2025 9/15/2025 11/10/2025
DATE SAMPLE REC'D 3/6/2025 5/8/2025 7/10/2025 9/11/2025 11/6/2025
DATE SAMPLED 3/4/2025 5/6/2025 7/8/2025 9/9/2025 11/4/2025
LAB NUMBER 3-1042 5-1188 7-1301 9-1425 11-1533
PRODUCT SAE 40 SAE 40 SAE 40 SAE 40 SAE 40
HOURS ON OIL 250 500 750 240 490
HOURS ON UNIT 4,120 4,370 4,620 4,860 5,110
VISC. SSU @ 100 F 547 563 588 543 554
VISC. KIN @ 100 F 118.0 121.4 126.9 117.2 119.6
VISC. SSU @ 210 F 65.9 66.4 67.8 65.6 66.1
PENTANE INSOLUBLES 0.08% 0.14% 0.31% 0.10% 0.13%
WATER BY DISTILLATION NIL NIL TRACE NIL NIL
FUEL DILUTION NIL NIL TRACE NIL NIL
Metals in p.p.m.
IRON 12 18 29 21 14
SILVER 0.0 0.0 0.0 0.0 0.0
ALUMINUM 3.0 4.2 11.4 5.1 3.3
CHROMIUM 1.2 1.5 2.8 1.9 1.3
COPPER 5.4 6.1 8.3 6.0 5.2
MAGNESIUM 142 138 131 155 149
SODIUM 8.1 8.6 10.9 9.0 8.3
NICKEL 0.0 0.0 0.3 0.1 0.0
LEAD 4.2 5.0 9.1 6.3 4.4
SILICON watch 6.0 9.2 34.0 12.1 7.0
TIN 0.0 0.0 0.2 0.1 0.0
TITANIUM 0.0 0.0 0.0 0.0 0.0
BORON 58 55 52 63 60
BARIUM 0.4 0.3 0.3 0.5 0.4
MOLYBDENUM 1.1 1.0 0.9 1.2 1.1
VANADIUM 0.0 0.0 0.1 0.0 0.0
ZINC 1180 1142 1098 1205 1176
MANGANESE 0.6 0.8 1.4 1.0 0.7
CALCIUM 2410 2355 2288 2465 2420
PHOSPHORUS 1035 1006 968 1058 1030

Lab numbers 3-1042 · 5-1188 · 7-1301 · 9-1425 · 11-1533. Specimen figures throughout — scroll the sheet sideways on a narrow screen.

Three ways to receive it

Printed 8½ × 11 sheets, email, or our online reporting system — whichever suits how your people work.

Customisable forms

The rows on a report are set up to match the equipment being monitored, not a fixed template.

A person's judgement

Every report carries a written comment from the analyst who reviewed it. Numbers without interpretation are not much use.